DTS-BLY-5S(ADV-10km) · Multimode 10 km DTS
10 km multimode sensing for power tunnels, utility corridors and industrial fire monitoring.
DTS-BLY-5S(ADV-10km) 10 km Distributed Temperature Sensing (DTS) System
DTS-BLY-5S(ADV-10km)
10 km Distributed Temperature Sensing (DTS) System

Measures continuous temperature profiles and abnormal-temperature locations along the fiber. Select range, fiber type, channels and sensing cable for the specified model.
Typical applications
Coal-mine surface facilities, power tunnels, metro electrical safety, nuclear power plants, renewable energy facilities, transportation tunnels, fire protection and fire detection, etc.
Spatial resolution, sampling interval and location accuracy are distinct quantities. Temperature accuracy depends on fiber length, acquisition time, temperature range and cable configuration; optimum values are not necessarily simultaneous.
Spatial resolution uses the 10%–90% step-response criterion and the ± spatial-extent notation used in this datasheet. Location accuracy is specified separately. Compare specifications using the same definitions and test conditions.
Technical specifications
| Parameter | Specification |
|---|---|
| Fiber Type | Multimode Fiber |
| Center Wavelength | 1550 nm |
| Measurement Range | 10 km |
| Spatial resolution | ±0.5 m |
| Location Accuracy | ±0.5 m |
| Measurement Time | ≤3 s/km(software-adjustable) / software-adjustable |
| Temperature Measurement Range | -40°C to 450°C (depending on cable type) Depending on cable type |
| Temperature Accuracy | ±0.1°C@2km, ±0.5°C @ 10 km; |
| Temperature Resolution | 0.01°C |
| Measurement Channels | Up to 16 channels |
| Optical Connector | FC/APC |
| Power Supply | DC 24 V; average power consumption ≤8 W |
| Operating Temperature | -10°C to 60°C |
| Storage Temperature | -20°C to 70°C |
| Communication Interfaces | 1 × RS-232, 1 × RJ45 Ethernet, 2 × RS-485, 8 relay outputs |
| Dimensions (W × D × H) | 482.6 × 442.7 × 88.8 mm (2U rack-mount) |
| Weight | 8 kg |
Applications and further reading
- Urban lifeline monitoring for excavation damage, underground pipelines and public safety
- Multi-hazard fiber sensing and rescue-support localization in underground coal mines
- Leakage and deformation monitoring for tailings dams and slurry pipelines
- Multi-parameter fiber monitoring for substation GIL, busbars and transformers
Discuss your project with our engineer
Corporate Sales TeamCorporate contact
Contact us ↗