Wuxi BrillouinBRILLOUIN · FIBER OPTIC SENSING
Home / Products & applications

DTS-BLY-5S(ADV-10km) · Multimode 10 km DTS

10 km multimode sensing for power tunnels, utility corridors and industrial fire monitoring.

DTS uses optical fiber as a continuous temperature sensor. Selected fire-suitable configurations up to 10 km and the fourth-generation 12 km configuration can apply the same sensing and installation principles to Fiber Optic Linear Heat Detection (LHD); alarm zones, thresholds, response, fault monitoring and fire-system interfaces must meet applicable fire-alarm requirements. Applicable EN 54-22 or GB 16280 product requirements and certifications such as CCCF depend on the final product and market. Existing 20/30 km long-range and oil/geothermal versions are not intended for this fire application.

DTS-BLY-5S(ADV-10km) 10 km Distributed Temperature Sensing (DTS) System

DTS-BLY-5S(ADV-10km)
10 km Distributed Temperature Sensing (DTS) System

DTS-BLY-5S(ADV-10km) · Multimode 10 km DTS

Measures continuous temperature profiles and abnormal-temperature locations along the fiber. Select range, fiber type, channels and sensing cable for the specified model.

Typical applications

Coal-mine surface facilities, power tunnels, metro electrical safety, nuclear power plants, renewable energy facilities, transportation tunnels, fire protection and fire detection, etc.

Spatial resolution, sampling interval and location accuracy are distinct quantities. Temperature accuracy depends on fiber length, acquisition time, temperature range and cable configuration; optimum values are not necessarily simultaneous.

Spatial resolution uses the 10%–90% step-response criterion and the ± spatial-extent notation used in this datasheet. Location accuracy is specified separately. Compare specifications using the same definitions and test conditions.

Technical specifications

ParameterSpecification
Fiber TypeMultimode Fiber
Center Wavelength1550 nm
Measurement Range10 km
Spatial resolution±0.5 m
Location Accuracy±0.5 m
Measurement Time≤3 s/km(software-adjustable) / software-adjustable
Temperature Measurement Range-40°C to 450°C (depending on cable type)
Depending on cable type
Temperature Accuracy±0.1°C@2km, ±0.5°C @ 10 km;
Temperature Resolution0.01°C
Measurement ChannelsUp to 16 channels
Optical ConnectorFC/APC
Power SupplyDC 24 V; average power consumption ≤8 W
Operating Temperature-10°C to 60°C
Storage Temperature-20°C to 70°C
Communication Interfaces1 × RS-232, 1 × RJ45 Ethernet, 2 × RS-485, 8 relay outputs
Dimensions (W × D × H)482.6 × 442.7 × 88.8 mm (2U rack-mount)
Weight8 kg

Applications and further reading

View all product specifications

Discuss your project with our engineer

李亚男

事业部经理

Contact us ↗

← Return to your home page